SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application

Danfoss Semco · Denmark

High-pressure water mist local application system for protecting specific hazardous equipment within engine rooms: main and auxiliary engines, boiler fronts, oil separators, and incinerators. Includes detection and release system. Activates automatically when sensors detect heat, smoke, or flame. Nozzles dimensioned in sections; all nozzles in the activated zone release simultaneously. Compact skid with small pipe dimensions and low water consumption.

Technical specifications

Agent Type
High-pressure water mist (pure fresh water)
Operating Pressure
100bar
Nozzle Type
Open nozzle for local application
Detection Type
Heat, smoke, or flame sensors (application dependent)
Activation Method
Automatic via detection system; manual override available
Material
AISI 316 stainless steel piping
System Configuration
Dry pipe with automatic activation per section
Protected Equipment
Main engines, auxiliary engines, boiler fronts, oil separators, incinerators
Safe for Electrical Equipment
Yes (IP 23 or better)

Certifications

  • BV
  • CCS
  • DNV
  • LR
  • MED
  • NK
  • SOLAS
  • USCG