FlameRanger Autonomous Robotic Fire Suppression System vs SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems
The Unifire FlameRanger Autonomous Robotic Fire Suppression System and Danfoss Semco SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) are both fire suppression systems products certified to SOLAS.
FlameRanger Autonomous Robotic Fire Suppression System
SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
Unifire ·
Specification comparison
| Specification | FlameRanger Autonomous Robotic Fire Suppression System | SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) |
|---|---|---|
| Response Time | <15 seconds | |
| Simultaneous Fire Tracking | 4 fires | |
| Robotic Nozzles Per System | 2 nozzles | |
| Detection Type | Triple IR flame detection (FGD IR3) + thermal imaging (VisionTIR FireTIR) | |
| Targeting | 3D dynamic fire localization and tracking | |
| Operation Mode | Fully autonomous with remote human override capability | |
| Agent Type | Water-based (compatible with foam) | |
| Software | Proprietary in-house designed electronics and software | |
| Remote Access | Global remote monitoring and override via web interface | |
| Nozzle ID | AB (5-12-44-68-20-57) | |
| Operating Pressure | 60 bar | |
| K-factor | 2.0 | |
| Flow Rate | 15.5 l/min | |
| Max Ceiling Height | 2.5 m | |
| Coverage Area | 12 (centric within cabin) m2 | |
| Activation Temperature | 57 C | |
| Orientation | Pendent | |
| Material | Nozzle head: CuZn36Pb2As (brass) NiSn coated; Top: AISI 316L | |
| Pipe Connection | 12mm DIN 2353 M12L | |
| Part Number | 8074115 |
Certification comparison
| Certification | FlameRanger Autonomous Robotic Fire Suppression System | SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) |
|---|---|---|
| DNV | — Not listed | ✓ |
| LR | — Not listed | ✓ |
| SOLAS | ✓ | ✓ |
Other Fire Suppression Systems comparisons
Data sources
SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
Data from components.semcomaritime.com ·
View original