FlameRanger Autonomous Robotic Fire Suppression System vs SEM-SAFE High-Pressure Water Mist System for Accommodation
Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems
The Unifire FlameRanger Autonomous Robotic Fire Suppression System and Danfoss Semco SEM-SAFE High-Pressure Water Mist System for Accommodation are both fire suppression systems products certified to SOLAS. Key difference: Agent Type — FlameRanger Autonomous Robotic Fire Suppression System is Water-based (compatible with foam) vs SEM-SAFE High-Pressure Water Mist System for Accommodation at High-pressure water mist (pure fresh water).
FlameRanger Autonomous Robotic Fire Suppression System
SEM-SAFE High-Pressure Water Mist System for Accommodation
Unifire ·
Specification comparison
| Specification | FlameRanger Autonomous Robotic Fire Suppression System | SEM-SAFE High-Pressure Water Mist System for Accommodation |
|---|---|---|
| Response Time | <15 seconds | |
| Simultaneous Fire Tracking | 4 fires | |
| Robotic Nozzles Per System | 2 nozzles | |
| Detection Type | Triple IR flame detection (FGD IR3) + thermal imaging (VisionTIR FireTIR) | |
| Targeting | 3D dynamic fire localization and tracking | |
| Operation Mode | Fully autonomous with remote human override capability | |
| Agent Type | Water-based (compatible with foam) | High-pressure water mist (pure fresh water) |
| Software | Proprietary in-house designed electronics and software | |
| Remote Access | Global remote monitoring and override via web interface | |
| Operating Pressure | 100 bar | |
| Standby Pressure | 10 - 15 bar | |
| Nozzle Type | Closed with glass bulb (automatic activation) | |
| Activation Temperature | 57 C | |
| Droplet Size | 10 - 50 micron | |
| Material | AISI 316 stainless steel piping | |
| Nozzle Spacing | Up to 5.5 m | |
| Max Ceiling Height | 2.5 m | |
| System Configuration | Wet pipe with pressurized standby | |
| Emergency Backup | Minimum 1 minute capacity at max required flow |
Certification comparison
| Certification | FlameRanger Autonomous Robotic Fire Suppression System | SEM-SAFE High-Pressure Water Mist System for Accommodation |
|---|---|---|
| BV | — Not listed | ✓ |
| CCS | — Not listed | ✓ |
| DNV | — Not listed | ✓ |
| LR | — Not listed | ✓ |
| MED | — Not listed | ✓ |
| NK | — Not listed | ✓ |
| SOLAS | ✓ | ✓ |
| USCG | — Not listed | ✓ |
Other Fire Suppression Systems comparisons
Data sources
SEM-SAFE High-Pressure Water Mist System for Accommodation
Data from ·