AquaMist ULF Marine Water Mist System vs SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems
The Tyco Fire Protection (Johnson Controls) AquaMist ULF Marine Water Mist System and Danfoss Semco SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) are both fire suppression systems products certified to SOLAS. Key difference: Operating Pressure — AquaMist ULF Marine Water Mist System is Up to 250 psi vs SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) at 60 bar.
AquaMist ULF Marine Water Mist System
SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
Unverified
Specification comparison
| Specification | AquaMist ULF Marine Water Mist System | SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) |
|---|---|---|
| System Type | Low-pressure water mist | |
| Operating Pressure | Up to 250 psi | 60 bar |
| Agent Type | Fresh water or seawater | |
| Nozzle Types | AM6, AM11, AM22, AM24, AM27, AM29, AM30, AM31, AM32, AM34 | |
| Configuration | Wet pipe, dry pipe, preaction, deluge | |
| Nozzle ID | AB (5-12-44-68-20-57) | |
| K-factor | 2.0 | |
| Flow Rate | 15.5 l/min | |
| Max Ceiling Height | 2.5 m | |
| Coverage Area | 12 (centric within cabin) m2 | |
| Activation Temperature | 57 C | |
| Orientation | Pendent | |
| Material | Nozzle head: CuZn36Pb2As (brass) NiSn coated; Top: AISI 316L | |
| Pipe Connection | 12mm DIN 2353 M12L | |
| Part Number | 8074115 |
Certification comparison
| Certification | AquaMist ULF Marine Water Mist System | SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) |
|---|---|---|
| DNV | — Not listed | ✓ |
| LR | — Not listed | ✓ |
| MED | ✓ | — Not listed |
| SOLAS | ✓ | ✓ |
Other Fire Suppression Systems comparisons
Data sources
SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
Data from components.semcomaritime.com ·
View original