ANSUL SAPPHIRE Marine Clean Agent System (Novec 1230) vs SEM-SAFE High-Pressure Water Mist System for Accommodation
Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems
The Tyco Fire Protection (Johnson Controls) ANSUL SAPPHIRE Marine Clean Agent System (Novec 1230) and Danfoss Semco SEM-SAFE High-Pressure Water Mist System for Accommodation are both fire suppression systems products certified to MED and SOLAS. Key difference: Agent Type — ANSUL SAPPHIRE Marine Clean Agent System (Novec 1230) is 3M Novec 1230 (FK-5-1-12) vs SEM-SAFE High-Pressure Water Mist System for Accommodation at High-pressure water mist (pure fresh water).
ANSUL SAPPHIRE Marine Clean Agent System (Novec 1230)
SEM-SAFE High-Pressure Water Mist System for Accommodation
Specification comparison
| Specification | ANSUL SAPPHIRE Marine Clean Agent System (Novec 1230) | SEM-SAFE High-Pressure Water Mist System for Accommodation |
|---|---|---|
| Agent Type | 3M Novec 1230 (FK-5-1-12) | High-pressure water mist (pure fresh water) |
| System Pressure | 25 (360 psi) / 42 / 70 bar | |
| Maximum Fill Density | 75 lbs/ft3 | |
| Minimum Design Concentration (Class B) | 5.85 % | |
| Maximum Nozzle Coverage Length | 9.75 m | |
| Temperature Range | 0 - 54 C | |
| Ozone Depletion Potential | 0.0 | |
| Global Warming Potential | 1.0 | |
| Atmospheric Lifetime | 5 days | |
| Operating Pressure | 100 bar | |
| Standby Pressure | 10 - 15 bar | |
| Nozzle Type | Closed with glass bulb (automatic activation) | |
| Activation Temperature | 57 C | |
| Droplet Size | 10 - 50 micron | |
| Material | AISI 316 stainless steel piping | |
| Nozzle Spacing | Up to 5.5 m | |
| Max Ceiling Height | 2.5 m | |
| System Configuration | Wet pipe with pressurized standby | |
| Emergency Backup | Minimum 1 minute capacity at max required flow |
Certification comparison
| Certification | ANSUL SAPPHIRE Marine Clean Agent System (Novec 1230) | SEM-SAFE High-Pressure Water Mist System for Accommodation |
|---|---|---|
| BV | — Not listed | ✓ |
| CCS | — Not listed | ✓ |
| DNV | — Not listed | ✓ |
| LR | — Not listed | ✓ |
| MED | ✓ | ✓ |
| NK | — Not listed | ✓ |
| SOLAS | ✓ | ✓ |
| USCG | — Not listed | ✓ |
Other Fire Suppression Systems comparisons
Data sources
SEM-SAFE High-Pressure Water Mist System for Accommodation