ANSUL R-102 Marine Galley Fire Suppression System vs SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)

Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems

The Tyco Fire Protection (Johnson Controls) ANSUL R-102 Marine Galley Fire Suppression System and Danfoss Semco SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57) are both fire suppression systems products certified to SOLAS.

ANSUL R-102 Marine Galley Fire Suppression System
SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)

Specification comparison

Specification ANSUL R-102 Marine Galley Fire Suppression System SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
Agent Type Low-pH liquid agent (ANSULEX)
Design Type Appliance-specific or overlapping
Protected Areas Hoods, ducts, plenums, filters, cooking appliances
Nozzle ID F (3-02-48-4-22-57)
Operating Pressure 100 bar
K-factor 2.04
Max Ceiling Height 2.5 m
Nozzle Spacing 2.5 m
Activation Temperature 57 C
Orientation Pendent
Max Distance to Bulkhead 1.25 m
Material CuZn36Pb2As (brass) coated with NiSn
Pipe Connection 10mm DIN 2353 M10S
Part Number 8068633

Certification comparison

Certification ANSUL R-102 Marine Galley Fire Suppression System SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
BV — Not listed ✓
DNV — Not listed ✓
LR — Not listed ✓
SOLAS ✓ ✓

Other Fire Suppression Systems comparisons

Data sources

ANSUL R-102 Marine Galley Fire Suppression System
Data from ·
SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
Data from components.semcomaritime.com ·
View original