ANSUL Marine INERGEN 200-Bar Inert Gas System vs SEM-SAFE Accommodation Nozzle Type D (HNMP-4-10-1.25-57)

Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems

The Tyco Fire Protection (Johnson Controls) ANSUL Marine INERGEN 200-Bar Inert Gas System and Danfoss Semco SEM-SAFE Accommodation Nozzle Type D (HNMP-4-10-1.25-57) are both fire suppression systems products certified to SOLAS.

ANSUL Marine INERGEN 200-Bar Inert Gas System
SEM-SAFE Accommodation Nozzle Type D (HNMP-4-10-1.25-57)

Specification comparison

Specification ANSUL Marine INERGEN 200-Bar Inert Gas System SEM-SAFE Accommodation Nozzle Type D (HNMP-4-10-1.25-57)
Agent Type INERGEN (52% N2, 40% Ar, 8% CO2)
System Pressure 200 bar
Fire Classes Class A, B, and C
Ozone Depletion Potential 0.0
Global Warming Potential 0.0
Nozzle ID D
Operating Pressure 100 bar
K-factor 1.25
Activation Temperature 57 C
Orientation Pendent
Material CuZn36Pb2As (brass) coated with NiSn
Pipe Connection 10mm DIN 2353 M10S

Certification comparison

Certification ANSUL Marine INERGEN 200-Bar Inert Gas System SEM-SAFE Accommodation Nozzle Type D (HNMP-4-10-1.25-57)
BV — Not listed ✓
DNV — Not listed ✓
LR — Not listed ✓
MED ✓ — Not listed
SOLAS ✓ ✓

Other Fire Suppression Systems comparisons

Data sources

ANSUL Marine INERGEN 200-Bar Inert Gas System
Data from ansul.com ·
View original
SEM-SAFE Accommodation Nozzle Type D (HNMP-4-10-1.25-57)
Data from components.semcomaritime.com ·
View original