NFF XFlow Galley and Duct System vs SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)

Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems

The Survitec NFF XFlow Galley and Duct System and Danfoss Semco SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57) are both fire suppression systems products. Key difference: Operating Pressure — NFF XFlow Galley and Duct System is ~14 bar vs SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57) at 100 bar.

NFF XFlow Galley and Duct System
SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)

Specification comparison

Specification NFF XFlow Galley and Duct System SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
Operating Pressure ~14 bar 100 bar
System Type Galley and duct water mist
Nozzle ID F (3-02-48-4-22-57)
K-factor 2.04
Max Ceiling Height 2.5 m
Nozzle Spacing 2.5 m
Activation Temperature 57 C
Orientation Pendent
Max Distance to Bulkhead 1.25 m
Material CuZn36Pb2As (brass) coated with NiSn
Pipe Connection 10mm DIN 2353 M10S
Part Number 8068633

Certification comparison

Certification NFF XFlow Galley and Duct System SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
BV — Not listed ✓
DNV — Not listed ✓
LR — Not listed ✓
MED ✓ — Not listed
SOLAS — Not listed ✓

Other Fire Suppression Systems comparisons

Data sources

NFF XFlow Galley and Duct System
Data from survitecgroup.com ·
View original
SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
Data from components.semcomaritime.com ·
View original