CO2 High-Pressure Extinguishing System vs SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems
The Minimax CO2 High-Pressure Extinguishing System and Danfoss Semco SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) are both fire suppression systems products certified to DNV and LR. Key difference: Coverage Area — CO2 High-Pressure Extinguishing System is Engine rooms, pump rooms, cargo holds vs SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) at 12 (centric within cabin) m2.
CO2 High-Pressure Extinguishing System
SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
Specification comparison
| Specification | CO2 High-Pressure Extinguishing System | SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) |
|---|---|---|
| Agent Type | Carbon Dioxide (CO2) | |
| System Type | High-pressure total flooding | |
| Detection Type | Smoke, heat, and flame detectors | |
| Activation | Automatic or manual | |
| Coverage Area | Engine rooms, pump rooms, cargo holds | 12 (centric within cabin) m2 |
| Monitoring | Gas quantity, shutoff, release and distribution units monitored | |
| Nozzle ID | AB (5-12-44-68-20-57) | |
| Operating Pressure | 60 bar | |
| K-factor | 2.0 | |
| Flow Rate | 15.5 l/min | |
| Max Ceiling Height | 2.5 m | |
| Activation Temperature | 57 C | |
| Orientation | Pendent | |
| Material | Nozzle head: CuZn36Pb2As (brass) NiSn coated; Top: AISI 316L | |
| Pipe Connection | 12mm DIN 2353 M12L | |
| Part Number | 8074115 |
Certification comparison
| Certification | CO2 High-Pressure Extinguishing System | SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) |
|---|---|---|
| BV | ✓ | — Not listed |
| DNV | ✓ | ✓ |
| LR | ✓ | ✓ |
| MED | ✓ | — Not listed |
| SOLAS | ✓ | ✓ |
Other Fire Suppression Systems comparisons
Data sources
SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
Data from components.semcomaritime.com ·
View original