HI-FOG Marine Spray Head vs SEM-SAFE High-Pressure Water Mist System for Accommodation
Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems
The Marioff HI-FOG Marine Spray Head and Danfoss Semco SEM-SAFE High-Pressure Water Mist System for Accommodation are both fire suppression systems products certified to DNV and LR. Key difference: Operating Pressure — HI-FOG Marine Spray Head is 80 - 140 bar vs SEM-SAFE High-Pressure Water Mist System for Accommodation at 100 bar.
HI-FOG Marine Spray Head
SEM-SAFE High-Pressure Water Mist System for Accommodation
Specification comparison
| Specification | HI-FOG Marine Spray Head | SEM-SAFE High-Pressure Water Mist System for Accommodation |
|---|---|---|
| Operating Pressure | 80 - 140 bar | 100 bar |
| Material | Stainless steel with strainer | AISI 316 stainless steel piping |
| Activation | System-activated via fire detection (no thermal element) | |
| Orifice Type | Open orifices | |
| Agent Type | High-pressure water mist (pure fresh water) | |
| Standby Pressure | 10 - 15 bar | |
| Nozzle Type | Closed with glass bulb (automatic activation) | |
| Activation Temperature | 57 C | |
| Droplet Size | 10 - 50 micron | |
| Nozzle Spacing | Up to 5.5 m | |
| Max Ceiling Height | 2.5 m | |
| System Configuration | Wet pipe with pressurized standby | |
| Emergency Backup | Minimum 1 minute capacity at max required flow |
Certification comparison
| Certification | HI-FOG Marine Spray Head | SEM-SAFE High-Pressure Water Mist System for Accommodation |
|---|---|---|
| BV | — Not listed | ✓ |
| CCS | — Not listed | ✓ |
| DNV | ✓ | ✓ |
| LR | ✓ | ✓ |
| MED | — Not listed | ✓ |
| NK | — Not listed | ✓ |
| SOLAS | ✓ | ✓ |
| USCG | — Not listed | ✓ |
Other Fire Suppression Systems comparisons