HI-FOG Marine Section Valves vs SEM-SAFE Bilge Nozzle Type BT (HNDP-0-12-1.26-00)

Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems

The Marioff HI-FOG Marine Section Valves and Danfoss Semco SEM-SAFE Bilge Nozzle Type BT (HNDP-0-12-1.26-00) are both fire suppression systems products certified to DNV and LR. Key difference: Operating Pressure — HI-FOG Marine Section Valves is 80 - 140 bar vs SEM-SAFE Bilge Nozzle Type BT (HNDP-0-12-1.26-00) at 60 bar.

HI-FOG Marine Section Valves
SEM-SAFE Bilge Nozzle Type BT (HNDP-0-12-1.26-00)

Specification comparison

Specification HI-FOG Marine Section Valves SEM-SAFE Bilge Nozzle Type BT (HNDP-0-12-1.26-00)
Operating Pressure 80 - 140 bar 60 bar
Normal State Normally open, constantly monitored
Material Stainless steel Nozzle head: CuZn36Pb2As (brass) NiSn coated; Top: AISI 316L
Test Connection Built-in maintenance test port
Nozzle ID BT
K-factor 1.258
Max Ceiling Height 1.5 m
Nozzle Spacing 2.7 x 3.0 m
Max Distance to Bulkhead Half spacing
Orientation Pendent
Pipe Connection 12mm DIN 2353 M12L
Part Number 8068629

Certification comparison

Certification HI-FOG Marine Section Valves SEM-SAFE Bilge Nozzle Type BT (HNDP-0-12-1.26-00)
DNV ✓ ✓
LR ✓ ✓
SOLAS ✓ ✓

Other Fire Suppression Systems comparisons

Data sources

HI-FOG Marine Section Valves
Data from marioff.com ·
View original
SEM-SAFE Bilge Nozzle Type BT (HNDP-0-12-1.26-00)
Data from components.semcomaritime.com ·
View original