Specification Natura Inert Gas Fire Suppression System (Marine) SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
Agent Type IG-541 (52% N2, 40% Ar, 8% CO2), IG-55, IG-100, IG-01
Temperature Range -20 to +54 C
Cylinder Standard ISO 9809-2
Valve Type Series 400 flow/pressure regulator
Piping Schedule 40
Application Type Total flood
Discharge Time <60 seconds
Nozzle ID AB (5-12-44-68-20-57)
Operating Pressure 60 bar
K-factor 2.0
Flow Rate 15.5 l/min
Max Ceiling Height 2.5 m
Coverage Area 12 (centric within cabin) m2
Activation Temperature 57 C
Orientation Pendent
Material Nozzle head: CuZn36Pb2As (brass) NiSn coated; Top: AISI 316L
Pipe Connection 12mm DIN 2353 M12L
Part Number 8074115

Certification comparison

Certification Natura Inert Gas Fire Suppression System (Marine) SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
DNV — Not listed ✓
LR — Not listed ✓
SOLAS — Not listed ✓

Other Fire Suppression Systems comparisons

Data sources

Natura Inert Gas Fire Suppression System (Marine)
Data from kidde-fenwal.com ·
View original
SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
Data from components.semcomaritime.com ·