Marine WHDR Wet Chemical Galley System vs SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)

Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems

The Kidde-Fenwal Marine WHDR Wet Chemical Galley System and Danfoss Semco SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) are both fire suppression systems products certified to DNV.

Marine WHDR Wet Chemical Galley System
SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)

Specification comparison

Specification Marine WHDR Wet Chemical Galley System SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
Agent Type Wet chemical (non-toxic)
Actuation Automatic or manual
Control System XV Control System
Max Containers 20
Temperature Range -18 to +49 C
Recharge On-board recharge capable
Nozzle ID AB (5-12-44-68-20-57)
Operating Pressure 60 bar
K-factor 2.0
Flow Rate 15.5 l/min
Max Ceiling Height 2.5 m
Coverage Area 12 (centric within cabin) m2
Activation Temperature 57 C
Orientation Pendent
Material Nozzle head: CuZn36Pb2As (brass) NiSn coated; Top: AISI 316L
Pipe Connection 12mm DIN 2353 M12L
Part Number 8074115

Certification comparison

Certification Marine WHDR Wet Chemical Galley System SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
DNV ✓ ✓
LR — Not listed ✓
SOLAS — Not listed ✓

Other Fire Suppression Systems comparisons

Data sources

Marine WHDR Wet Chemical Galley System
Data from kidde-fenwal.com ·
View original
SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
Data from components.semcomaritime.com ·
View original