Marine ADS Clean Agent Fire Suppression System vs SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)

Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems

The Kidde-Fenwal Marine ADS Clean Agent Fire Suppression System and Danfoss Semco SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57) are both fire suppression systems products.

Marine ADS Clean Agent Fire Suppression System
SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)

Specification comparison

Specification Marine ADS Clean Agent Fire Suppression System SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
Agent Type Novec 1230 or FM-200 (HFC-227ea)
Driver Gas Nitrogen
Flow Rate Improvement 2.5 - 3x vs standard
Storage Pressure Options 360 / 500 psi
Discharge Time 10 seconds
Application Type Total flood
Nozzle ID F (3-02-48-4-22-57)
Operating Pressure 100 bar
K-factor 2.04
Max Ceiling Height 2.5 m
Nozzle Spacing 2.5 m
Activation Temperature 57 C
Orientation Pendent
Max Distance to Bulkhead 1.25 m
Material CuZn36Pb2As (brass) coated with NiSn
Pipe Connection 10mm DIN 2353 M10S
Part Number 8068633

Certification comparison

Certification Marine ADS Clean Agent Fire Suppression System SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
BV — Not listed ✓
DNV — Not listed ✓
LR — Not listed ✓
SOLAS — Not listed ✓
USCG ✓ — Not listed

Other Fire Suppression Systems comparisons

Data sources

Marine ADS Clean Agent Fire Suppression System
Data from kidde-fenwal.com ·
View original
SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
Data from components.semcomaritime.com ·