Marine ADS Clean Agent Fire Suppression System vs SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application

Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems

The Kidde-Fenwal Marine ADS Clean Agent Fire Suppression System and Danfoss Semco SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application are both fire suppression systems products certified to USCG. Key difference: Agent Type — Marine ADS Clean Agent Fire Suppression System is Novec 1230 or FM-200 (HFC-227ea) vs SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application at High-pressure water mist (pure fresh water).

Marine ADS Clean Agent Fire Suppression System
SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application

Specification comparison

Specification Marine ADS Clean Agent Fire Suppression System SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application
Agent Type Novec 1230 or FM-200 (HFC-227ea) High-pressure water mist (pure fresh water)
Driver Gas Nitrogen
Flow Rate Improvement 2.5 - 3x vs standard
Storage Pressure Options 360 / 500 psi
Discharge Time 10 seconds
Application Type Total flood
Operating Pressure 100 bar
Nozzle Type Open nozzle for local application
Detection Type Heat, smoke, or flame sensors (application dependent)
Activation Method Automatic via detection system; manual override available
Material AISI 316 stainless steel piping
System Configuration Dry pipe with automatic activation per section
Protected Equipment Main engines, auxiliary engines, boiler fronts, oil separators, incinerators
Safe for Electrical Equipment Yes (IP 23 or better)

Certification comparison

Certification Marine ADS Clean Agent Fire Suppression System SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application
BV — Not listed ✓
CCS — Not listed ✓
DNV — Not listed ✓
LR — Not listed ✓
MED — Not listed ✓
NK — Not listed ✓
SOLAS — Not listed ✓
USCG ✓ ✓

Other Fire Suppression Systems comparisons

Data sources

Marine ADS Clean Agent Fire Suppression System
Data from kidde-fenwal.com ·
View original
SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application
Data from ttr-cms.ttrbilisim.com.tr ·
View original