Hiller Water Mist FIRE-SCOPE 5000 vs SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)

Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems

The The Hiller Companies Hiller Water Mist FIRE-SCOPE 5000 and Danfoss Semco SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57) are both fire suppression systems products. Key difference: Operating Pressure — Hiller Water Mist FIRE-SCOPE 5000 is 750 psig vs SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57) at 100 bar.

Hiller Water Mist FIRE-SCOPE 5000
SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)

Specification comparison

Specification Hiller Water Mist FIRE-SCOPE 5000 SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
Agent Type Water mist (single-fluid)
Operating Pressure 750 psig 100 bar
Droplet Size 150 micron
Coverage Area Up to 17,000 (machinery) / 42,000 (turbine) ft3
Pump Options Gas-driven (nitrogen + stainless steel piston) or electric (positive displacement)
Piping Small diameter tubing/pipe
Nozzle ID F (3-02-48-4-22-57)
K-factor 2.04
Max Ceiling Height 2.5 m
Nozzle Spacing 2.5 m
Activation Temperature 57 C
Orientation Pendent
Max Distance to Bulkhead 1.25 m
Material CuZn36Pb2As (brass) coated with NiSn
Pipe Connection 10mm DIN 2353 M10S
Part Number 8068633

Certification comparison

Certification Hiller Water Mist FIRE-SCOPE 5000 SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
BV — Not listed ✓
DNV — Not listed ✓
LR — Not listed ✓
SOLAS — Not listed ✓
USCG ✓ — Not listed

Other Fire Suppression Systems comparisons

Data sources

Hiller Water Mist FIRE-SCOPE 5000
Data from hillerfire.com ·
View original
SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
Data from components.semcomaritime.com ·
View original