SEM-SAFE Cabin Sidewall Nozzle Type Z vs SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)

Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems

The Danfoss Semco SEM-SAFE Cabin Sidewall Nozzle Type Z and Danfoss Semco SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57) are both fire suppression systems products certified to DNV and LR. Key difference: Nozzle ID — SEM-SAFE Cabin Sidewall Nozzle Type Z is Z vs SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57) at F (3-02-48-4-22-57).

SEM-SAFE Cabin Sidewall Nozzle Type Z
SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)

Specification comparison

Specification SEM-SAFE Cabin Sidewall Nozzle Type Z SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
Nozzle ID Z F (3-02-48-4-22-57)
Operating Pressure 60 bar 100 bar
K-factor 4.5 2.04
Max Ceiling Height 2.5 m 2.5 m
Coverage Area 4 x 6 (width x length) m
Activation Temperature 57 C 57 C
Orientation Sidewall Pendent
Nozzle Position Max 150mm below ceiling
Material Nozzle head: CuZn36Pb2As (brass) NiSn coated; Top: AISI 316L CuZn36Pb2As (brass) coated with NiSn
Pipe Connection 12mm DIN 2353 M12L 10mm DIN 2353 M10S
Part Number 8077172 8068633
Nozzle Spacing 2.5 m
Max Distance to Bulkhead 1.25 m

Certification comparison

Certification SEM-SAFE Cabin Sidewall Nozzle Type Z SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
BV — Not listed ✓
DNV ✓ ✓
LR ✓ ✓
SOLAS ✓ ✓

Other Fire Suppression Systems comparisons

Data sources

SEM-SAFE Cabin Sidewall Nozzle Type Z
Data from components.semcomaritime.com ·
View original
SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
Data from components.semcomaritime.com ·
View original