SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57) vs SEM-SAFE High-Pressure Water Mist System for Accommodation

Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems

The Danfoss Semco SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57) and Danfoss Semco SEM-SAFE High-Pressure Water Mist System for Accommodation are both fire suppression systems products certified to BV and DNV. Key difference: Nozzle Spacing — SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57) is 2.5 m vs SEM-SAFE High-Pressure Water Mist System for Accommodation at Up to 5.5 m.

SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
SEM-SAFE High-Pressure Water Mist System for Accommodation

Specification comparison

Specification SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57) SEM-SAFE High-Pressure Water Mist System for Accommodation
Nozzle ID F (3-02-48-4-22-57)
Operating Pressure 100 bar 100 bar
K-factor 2.04
Max Ceiling Height 2.5 m 2.5 m
Nozzle Spacing 2.5 m Up to 5.5 m
Activation Temperature 57 C 57 C
Orientation Pendent
Max Distance to Bulkhead 1.25 m
Material CuZn36Pb2As (brass) coated with NiSn AISI 316 stainless steel piping
Pipe Connection 10mm DIN 2353 M10S
Part Number 8068633
Agent Type High-pressure water mist (pure fresh water)
Standby Pressure 10 - 15 bar
Nozzle Type Closed with glass bulb (automatic activation)
Droplet Size 10 - 50 micron
System Configuration Wet pipe with pressurized standby
Emergency Backup Minimum 1 minute capacity at max required flow

Certification comparison

Certification SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57) SEM-SAFE High-Pressure Water Mist System for Accommodation
BV ✓ ✓
CCS — Not listed ✓
DNV ✓ ✓
LR ✓ ✓
MED — Not listed ✓
NK — Not listed ✓
SOLAS ✓ ✓
USCG — Not listed ✓

Other Fire Suppression Systems comparisons

Data sources

SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
Data from components.semcomaritime.com ·
View original
SEM-SAFE High-Pressure Water Mist System for Accommodation
Data from ·