SEM-SAFE High-Pressure Water Mist System for Engine Room Total Flooding vs SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems
The Danfoss Semco SEM-SAFE High-Pressure Water Mist System for Engine Room Total Flooding and Danfoss Semco SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) are both fire suppression systems products certified to DNV and LR. Key difference: Operating Pressure — SEM-SAFE High-Pressure Water Mist System for Engine Room Total Flooding is 100 bar vs SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) at 60 bar.
SEM-SAFE High-Pressure Water Mist System for Engine Room Total Flooding
SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
Specification comparison
| Specification | SEM-SAFE High-Pressure Water Mist System for Engine Room Total Flooding | SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) |
|---|---|---|
| Agent Type | High-pressure water mist (pure fresh water) | |
| Operating Pressure | 100 bar | 60 bar |
| Nozzle Type | Open deluge nozzle | |
| Droplet Size | 10 - 50 micron | |
| Material | AISI 316 stainless steel piping | Nozzle head: CuZn36Pb2As (brass) NiSn coated; Top: AISI 316L |
| System Configuration | Dry pipe with manual activation (total flooding) | |
| Activation Method | Manual from valve operation panel (VOP) or bridge mimic panel | |
| Safe for Personnel | Yes (pure water, non-toxic) | |
| Safe for Electrical Equipment | Yes (IP 23 or better) | |
| Nozzle ID | AB (5-12-44-68-20-57) | |
| K-factor | 2.0 | |
| Flow Rate | 15.5 l/min | |
| Max Ceiling Height | 2.5 m | |
| Coverage Area | 12 (centric within cabin) m2 | |
| Activation Temperature | 57 C | |
| Orientation | Pendent | |
| Pipe Connection | 12mm DIN 2353 M12L | |
| Part Number | 8074115 |
Certification comparison
| Certification | SEM-SAFE High-Pressure Water Mist System for Engine Room Total Flooding | SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) |
|---|---|---|
| BV | ✓ | — Not listed |
| CCS | ✓ | — Not listed |
| DNV | ✓ | ✓ |
| LR | ✓ | ✓ |
| MED | ✓ | — Not listed |
| NK | ✓ | — Not listed |
| SOLAS | ✓ | ✓ |
| USCG | ✓ | — Not listed |