SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application vs SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)

Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems

The Danfoss Semco SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application and Danfoss Semco SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57) are both fire suppression systems products certified to BV and DNV. Key difference: Material — SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application is AISI 316 stainless steel piping vs SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57) at CuZn36Pb2As (brass) coated with NiSn.

SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application
SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)

Specification comparison

Specification SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
Agent Type High-pressure water mist (pure fresh water)
Operating Pressure 100 bar 100 bar
Nozzle Type Open nozzle for local application
Detection Type Heat, smoke, or flame sensors (application dependent)
Activation Method Automatic via detection system; manual override available
Material AISI 316 stainless steel piping CuZn36Pb2As (brass) coated with NiSn
System Configuration Dry pipe with automatic activation per section
Protected Equipment Main engines, auxiliary engines, boiler fronts, oil separators, incinerators
Safe for Electrical Equipment Yes (IP 23 or better)
Nozzle ID F (3-02-48-4-22-57)
K-factor 2.04
Max Ceiling Height 2.5 m
Nozzle Spacing 2.5 m
Activation Temperature 57 C
Orientation Pendent
Max Distance to Bulkhead 1.25 m
Pipe Connection 10mm DIN 2353 M10S
Part Number 8068633

Certification comparison

Certification SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
BV ✓ ✓
CCS ✓ — Not listed
DNV ✓ ✓
LR ✓ ✓
MED ✓ — Not listed
NK ✓ — Not listed
SOLAS ✓ ✓
USCG ✓ — Not listed

Other Fire Suppression Systems comparisons

Data sources

SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application
Data from ttr-cms.ttrbilisim.com.tr ·
View original
SEM-SAFE Accommodation Nozzle Type F (HNMP-4-10-2.04-57)
Data from components.semcomaritime.com ·
View original