SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application vs SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)

Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems

The Danfoss Semco SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application and Danfoss Semco SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) are both fire suppression systems products certified to DNV and LR. Key difference: Operating Pressure — SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application is 100 bar vs SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) at 60 bar.

SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application
SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)

Specification comparison

Specification SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
Agent Type High-pressure water mist (pure fresh water)
Operating Pressure 100 bar 60 bar
Nozzle Type Open nozzle for local application
Detection Type Heat, smoke, or flame sensors (application dependent)
Activation Method Automatic via detection system; manual override available
Material AISI 316 stainless steel piping Nozzle head: CuZn36Pb2As (brass) NiSn coated; Top: AISI 316L
System Configuration Dry pipe with automatic activation per section
Protected Equipment Main engines, auxiliary engines, boiler fronts, oil separators, incinerators
Safe for Electrical Equipment Yes (IP 23 or better)
Nozzle ID AB (5-12-44-68-20-57)
K-factor 2.0
Flow Rate 15.5 l/min
Max Ceiling Height 2.5 m
Coverage Area 12 (centric within cabin) m2
Activation Temperature 57 C
Orientation Pendent
Pipe Connection 12mm DIN 2353 M12L
Part Number 8074115

Certification comparison

Certification SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
BV ✓ — Not listed
CCS ✓ — Not listed
DNV ✓ ✓
LR ✓ ✓
MED ✓ — Not listed
NK ✓ — Not listed
SOLAS ✓ ✓
USCG ✓ — Not listed

Other Fire Suppression Systems comparisons

Data sources

SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application
Data from ttr-cms.ttrbilisim.com.tr ·
View original
SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
Data from components.semcomaritime.com ·