SEM-SAFE High-Pressure Water Mist System for Bilge Protection vs SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application

Fire Suppression Systems comparison · 2 products · View all Fire Suppression Systems

The Danfoss Semco SEM-SAFE High-Pressure Water Mist System for Bilge Protection and Danfoss Semco SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application are both fire suppression systems products certified to DNV and LR. Key difference: Operating Pressure — SEM-SAFE High-Pressure Water Mist System for Bilge Protection is 60 bar vs SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application at 100 bar.

SEM-SAFE High-Pressure Water Mist System for Bilge Protection
SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application

Specification comparison

Specification SEM-SAFE High-Pressure Water Mist System for Bilge Protection SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application
Agent Type High-pressure water mist (pure fresh water) High-pressure water mist (pure fresh water)
Operating Pressure 60 bar 100 bar
Nozzle Type BT (dedicated bilge nozzle) Open nozzle for local application
Max Ceiling Height 1.5 m
Nozzle Spacing 2.7 x 3.0 m
K-factor 1.258
Material Nozzle head: CuZn36Pb2As (brass) NiSn coated; Top: AISI 316L AISI 316 stainless steel piping
Pipe Connection 12mm DIN 2353 M12L
Detection Type Heat, smoke, or flame sensors (application dependent)
Activation Method Automatic via detection system; manual override available
System Configuration Dry pipe with automatic activation per section
Protected Equipment Main engines, auxiliary engines, boiler fronts, oil separators, incinerators
Safe for Electrical Equipment Yes (IP 23 or better)

Certification comparison

Certification SEM-SAFE High-Pressure Water Mist System for Bilge Protection SEM-SAFE High-Pressure Water Mist System for Engine Room Local Application
BV — Not listed ✓
CCS — Not listed ✓
DNV ✓ ✓
LR ✓ ✓
MED ✓ ✓
NK — Not listed ✓
SOLAS ✓ ✓
USCG — Not listed ✓