The Danfoss Semco SEM-SAFE High-Pressure Water Mist System for Accommodation and Danfoss Semco SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) are both fire suppression systems products certified to DNV and LR. Key difference: Operating Pressure — SEM-SAFE High-Pressure Water Mist System for Accommodation is 100 bar vs SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57) at 60 bar.

SEM-SAFE High-Pressure Water Mist System for Accommodation
SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)

Specification comparison

Specification SEM-SAFE High-Pressure Water Mist System for Accommodation SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
Agent Type High-pressure water mist (pure fresh water)
Operating Pressure 100 bar 60 bar
Standby Pressure 10 - 15 bar
Nozzle Type Closed with glass bulb (automatic activation)
Activation Temperature 57 C 57 C
Droplet Size 10 - 50 micron
Material AISI 316 stainless steel piping Nozzle head: CuZn36Pb2As (brass) NiSn coated; Top: AISI 316L
Nozzle Spacing Up to 5.5 m
Max Ceiling Height 2.5 m 2.5 m
System Configuration Wet pipe with pressurized standby
Emergency Backup Minimum 1 minute capacity at max required flow
Nozzle ID AB (5-12-44-68-20-57)
K-factor 2.0
Flow Rate 15.5 l/min
Coverage Area 12 (centric within cabin) m2
Orientation Pendent
Pipe Connection 12mm DIN 2353 M12L
Part Number 8074115

Certification comparison

Certification SEM-SAFE High-Pressure Water Mist System for Accommodation SEM-SAFE Cabin Nozzle Type AB (HNDP-0-12-2.0-57)
BV ✓ — Not listed
CCS ✓ — Not listed
DNV ✓ ✓
LR ✓ ✓
MED ✓ — Not listed
NK ✓ — Not listed
SOLAS ✓ ✓
USCG ✓ — Not listed